A Discussion of Low Reynolds Number Flow for the Two-Dimensional Benchmark Test Case

Miaocheng Weng,Peter V Nielsen,Li Liu
2012-01-01
Abstract:The use of CFD in ventilation research has arrived to a high level, but there are some conditions in the general CFD procedure which do not apply to all situations in the ventilation research. An example of this is the turbulence models in Reynolds-averaged Navier-Stokes equations, ie (RANS) equations.The flow in a ventilated room is generally assumed to be a fully developed turbulent flow, and this flow can be handled by most turbulence models. But in some areas of the room, including the occupied zone, a low Reynolds number flow can exist at a low room air supply velocity. Figure 1 shows measurements of the maximum velocity in the occupied zone of a room with mixing ventilation from a wall-mounted diffuser versus the air change rate. The flow is isothermal (Nielsen, 1992). Similarity principles state that any velocity, eg the maximum velocity in the occupied zone, is a linear function of the air change rate (or the supply velocity) when the flow is a fully developed isothermal turbulent flow. In Figure 1 this is the case for velocities larger than 0.25 m/s, but the figure indicates that the flow in the occupied zone is a low Reynolds number flow for velocities below 0.25 m/s (dotted line). The conventional turbulence models cannot accurately capture the flow in this low Reynolds number regime. On the other hand, an air change rate up to 5 covers most of the practical cases in air conditioning.