Distribution Parameter Extract of 500 Kv Current-limiting Inductors

CHEN Shui-ming,GENG Yi-nan,ZHANG Bo,WANG Zhen-xing,GE Cheng
DOI: https://doi.org/10.13336/j.1003-6520.hve.2009.04.012
2009-01-01
Abstract:Air-cored current-limiting inductor (CLI) is used to limit the magnitude of fault current in 500 kV power systems. While analyzing the potential distribution of CLI under work and impulse voltage, the distribution parameters is needed. The distribution distributions of CLI are calculated with FEM-analytic method (finite element method-analytic method) in this paper. The results show that the self capacitance of two terminals is little larger than the middle, and the mutual capacitance is almost similar. The capacitance of nearby two coils is larger than others, and the equivalent capacitance is 1.378 nF, while the equivalent capacitance to ground is 0.27 nF.