Development and application of internal fault analysis and calculation software for large-scale generator

孙宇光,黄子果,李晖,余波,洪心,张新平,封孝松,刘洪
DOI: https://doi.org/10.3969/j.issn.1006-6047.2014.02.026
2014-01-01
Abstract:The multi-loop analysis method for the internal faults of AC machines is fully validated by various experiments, based on which, a kind of visualized internal fault analysis software is developed for large-scale generators and its main functions and features are briefly introduced. It detects conveniently the type and location of any possible internal short circuit of generator, carries out the accurate transient or steady-state simulative calculations, checks comprehensively and intuitively the simulative results, examines the sensitivity of main protection and analyzes its performances. Some typical internal faults that may occur in a generator of Xiangjiaba hydropower station are simulated and analyzed, the types and current distributions of generator internal faults within the operational dead zones of widely-used main protections are summarized, and the causes of their low sensitivity are also introduced.
What problem does this paper attempt to address?