Insulation Status Diagnosis On Metal-Enclosed Switchgear Via Tev Sensing Network

Hongjing Liu,Ming Ren,Wenguang Huang,Wei Li,Zhigang Ren,Ming Dong
DOI: https://doi.org/10.1145/3158233.3159336
2015-01-01
Abstract:Metal enclosed switchgears, which have been widely used, play an important role in power distribution network, their safety operation is directively related to the reliability of power system as well as the power quality in consumer side. Partial discharges (PDs) detection is an effective way to identify potential faults and it can be detected for insulation diagnosis for metal-enclosed switchgear. Transient earth voltage( TEV) method as a non-intrusive method has the great engineering application value for estimating insulation condition of switchgear. In this present work, an innovative on-line insulation status diagnosis on metal-enclosed switchgear is proposed and performed with a self-adapting TEV sensing network. The built of TEV sensing network and PD diagnosis in three modes based on the self-adapting TEV sensing network are described in this paper.
What problem does this paper attempt to address?