Comprehensive Detection of Partial Discharge in Switchgear Using TEV

REN Ming,PENG Hua-dong,CHEN Xiao-qing,DONG Ming
DOI: https://doi.org/10.13336/j.1003-6520.hve.2010.10.022
2010-01-01
Abstract:In order to solve the problems such as single judgment criterion,low reliability of measurement in detection of PD in HV switchboard,we analyzed the method on how to better utilize TEV(transient earth voltage)in scientific research.Based on research results on TEV principle,comprehensive measurement was used to check and analyze typical defects in switchgear.Through researching the relationship among the temporal phases,number of pulses and threshold of measuring,and extracting the features corresponding to different typical defects,it is revealed that the needle discharge occurs at 0°~90°and 200°~340°with low appearance probability under high measurement threshold;internal discharge occurs at 0°~90°and 270°~315°,and similar decreasing trends are found under increasing of the threshold in the two regions;suspended discharge occurs at 0°~135°and 180°~315°,and has faster decreasing process in negative half periods comparing with the positive under increasing of the measurement threshold.These results accord with the conclusions which are obtained by using the traditional pulse current method.Consequently,it is possible to use TEV method to make identification of defects in HV switchboard.