One-order Integral Model of Refrigerants Flowing Through Adiabatic Capillary Tubes

Chunlu ZHANG,Guoliang DING
DOI: https://doi.org/10.3969/j.issn.1005-0930.2000.02.011
2000-01-01
Abstract:Two phase flow in adiabatic capillary tubes is generally described by partial differential equations and solved with finite difference method. In the work, an one order approximant for the mapping between the pressure and the specific volume in two phase regime was presented by Taylor series expansion. As a result, an one order approximate integral solution to the flow performance of adiabatic capillary tubes was obtained. The new model was compared with the distributed parameter model under the common working conditions of refrigeration and air conditioning. Three refrigerants CFC 12, HFC 134a and HC 600a are used as working fluids. The average deviations between the new model and the distributed parameter one falls into 1%. The computation speed of the new model is more than one order of magnitude higher than that of the distributed parameter one. In addition, the new model was used to predict the experimental mass flow rates through adiabatic capillary tubes. The consistency between the calculated values and the experimental ones is also satisfactory.
What problem does this paper attempt to address?