Experimental Study on Wood Crib Fire Suppression with Water Mist

刘江虹,廖光煊,厉培德,陆强
DOI: https://doi.org/10.3969/j.issn.1009-0029.2004.01.008
2004-01-01
Fire Science and Technology
Abstract:In order to study the mechanisms and effectivity of solid fire extinction with water mist,a series of experiments were conducted in a 3 m×3 m×3 m confined space.Fire sources are two dimensions of wood cribs.Before and after the application of water mist,some K-type thermocouples along the wood crib up-surface centerline and an infrared thermography were used to measure and visualize flame temperature and a turbine flux sensor were used to measure the application rate of water,respectively.The experimental results show that the flame of wood crib can not be extinguished in most time while the pressures are lower than 0.2 MPa,and the distance between flame and the water mist nozzle,the application rate of water are two main factors which influence the effectivity of wood crib fire extinction when the working pressure is low.In addition,the larger the wood crib dimension is,the easier the flame can be extinguished.
What problem does this paper attempt to address?