Novel Distributed Lightning Fault Location Method for Transmission Line Based on Non-contact Measurement Device of Lightning Current

YAO Chenguo,WU Hao,WANG Qi,LONG Yi,MA Yi,SHEN Yuan
DOI: https://doi.org/10.13336/j.1003-6520.hve.2014.09.039
2014-01-01
Abstract:Transmission lines are thousands of miles long, so artificially searching lightning fault points on the lines is time-consuming and uneconomic. Therefore, adopting the non-contact measurement device of lightning current and combining with the traveling wave fault location, we proposed a distributed lightning fault location method. According to difference in wave polarity among the three phases, we put forward the lightning pattern recognition among lightning striking the ground wire, the tower or the phase. As for shielding failures, we firstly determined whether the flashover happened or not, and determined the lightning range and flashover side if it happened. Then we deduced formulas for locating lightning and flashover in different lightning ranges. By using the wavelet packet transform(WPT), the wave arrival time was extracted for calculation. Simulations in EMTP-ATP show that, using the proposed method, the lightning fault location of transmission line can be calculated accurately, and the errors of striking point and flashover point are both less than 0.4%. Thus the proposed method is applicable.
What problem does this paper attempt to address?