Abstract:The theoretical analysis of the influence of different transposition forms on the coupling between two circuits which constitute two circuits on same tower is given and an investigation model for two circuits on same tower is established.When one circuit of the two circuits is shut down to be examined and repaired,the voltage and current which are induced in the shut down circuit by the coupling from the another circuit which operates under both normal and accident condition,are calculated by EMTP,the calculation results show that the transposition form is the determinant which influences the coupling between the two circuits.When fault occurs in electroficated circuit of the two circuits,more strict protective measures should be applied to the shut down circuit. Some points for attention in the practical operation are put forward.