Research on Corrosion Diagnostic Model of Grounding Grid Based on Tellegen's Theorem

Xin An Wu,Li Xue Li,Yi Hui Zheng,Xin Wang,De Min Cui,Jing Sun
DOI: https://doi.org/10.4028/www.scientific.net/amm.672-674.783
2014-01-01
Applied Mechanics and Materials
Abstract:Grounding grid was considered as a pure-resistor network and its inner information was obtained through limited grounding leads. A set of diagnostic equations was established based on Tellegen’s theorem. Iteration method and Nonnegative Least Squares method (NNLS) were used to solve it. To verify this method, corrosion diagnosis of single-branch and two-branch was simulated. An optimal plan was proposed in the simulating calculation, which diagnosed step by step and added measurement nodes according to the result of each step. This method is able to determine the corrosion position and degree reliably and the optimal plan has higher efficiency and less workload.
What problem does this paper attempt to address?