Simulation on interface airflow by occupant's traffic flow through operating room
Bin Zhou Jie Xia Hui Ren Ang Wang Ke Xue Mei-Lan Tan Su-Juan Shi a Department of HVAC,College of Urban Construction,Nanjing Tech University,Nanjing,Chinab National Air Cleaner & Gas Detect Production Quality Supervision and Inspection Center (Jiangsu),Suzhou,Chinac Suzhou Institute of Metrology,Suzhou,ChinaBin Zhou is a professor at Nanjing Tech University. His research interests include cleanroom Technology and Air Filtration. He has served as Chinese delegation member of ISO/TC142 WG04 HEPA/ULPA,member of National Standardized Committee for Cleanrooms and Associated Controlled Environments (SAC/TC 319). He was granted with the 2021 Jiangsu Provincial Science and Technology Award.Jie Xia is a master candidate from Nanjing Tech University,China. He is interested in pollution control in operating theatre and urban tunnel.Hui Ren is a master candidate from Nanjing Tech University,China. He is interested in air filtration and ventilation for indoor environment.Ang Wang is a master candidate from Nanjing Tech University,China. He is interested in thermal comfort in clean operating theatre.Ke Xue is a master from Nanjing Tech University,China. He is interested in dynamic simulation of indoor environment,especially in operating theatre.Mei-Lan Tan is a lecturer at Nanjing Tech University. She is interested in thermal comfort study.Su-Juan Shi is an associate professor at Suzhou Institute of Metrology. She is interested in cleanroom technology.
DOI: https://doi.org/10.1080/14733315.2024.2406155
2024-09-22
International Journal of Ventilation
Abstract:Air cleanliness level in operating room is crucial for safety of patient. Medical staffs usually enter or leave operating room under operational condition. However, the combined effect of traffic flow and temperature difference on airflow characteristic and particle dispersion through the door interface has not been fully investigated. Therefore, numerical simulation was carried out to investigate the influence of traffic flow and temperature difference. It is found that the disturbance caused by occupant's movement through the door interface is larger than that of the temperature difference. The larger the walking speed is, the more the infiltrated air and the intruded particles are. On average, the particle intrusion ratio with walking speed 0.60 m/s is less than that with walking speed 0.80 m/s and 1.00 m/s by 30% and 42%, respectively. It is recommended to slow down the walking speed when people enter into or leave the operating room. When people enter into the operating room, the particle intrusion ratio can be reduced with the increase of the temperature difference. It is suggested that the temperature in operating room should be larger appropriately than that of the anteroom. This study provides a reference for optimal operation of operating room.
energy & fuels,construction & building technology