Analysis of Thermal Capacity for Busbar Trunking System by Coupled Magneto-Fluid-thermal Field Calculation

武安波,张国刚,王建华,陈德桂,耿英三
DOI: https://doi.org/10.3969/j.issn.1003-3076.2002.03.016
2002-01-01
Abstract:The temperature rise of busbar trunking system is a fatal factor that affects its service performance. In this paper, a coupled magneto-fluid-thermal finite element analysis model is presented for the evaluation of electrical heating and natural convection for busbar trunking system. The power-frequency harmonic magnetic field, eddy currents and power loss of an air-insulated 3-phase/4-pole busbar trunking system are calculated firstly, and then the Joule heat is coupled into the fluid field analysis as heat generation load. Thermal analysis is directly coupled with fluid analysis. With the same source current and outer shielding, the temperature rise of busbars will increase when the space between the busbars is too big or too small, that is, there is a best midterm space between the busbars that can make the temperature rise lowest. The bigger the size of the steel shielding, the lower the temperature rise of the busbars.
What problem does this paper attempt to address?