Treatment of bio-hazardous wastewater by fenton oxidation combined with coagulation/ flocculation pretreatment: A case study

Jingchao Han,Xiang Liu,NanZhen Yang,Juliana Akit Ramsay,Yan Liu,Wei Jin
2011-01-01
Fresenius environmental bulletin
Abstract:A vehicle mounted full-scale facility with a sequential combination of coagulation/flocculation (CF) and Fenton oxidation (FO) processes was used to treat BHW from thirteen biotechnology enterprises. The facility with a capacity of 6 tonnes/day consisted of three stages: pH adjustment, CF pretreatment and FO. The appropriate conditions with a view to practical application were as follows: 70 mg/l of polymeric aluminum ferric chloride sulfate (PAFCS) for CF; 1.5 g/l of H(2)O(2) at initial pH 3.5 and 12 degrees C for FO. The [H(2)O(2)]/[Fe(2+)] molar ratio was controlled at 20 throughout all FO experiments. After continuous operation for 30 days at 6.3+/-5.1 degrees C, the average total plate count (TPC), adenosine triphosphate (ATP) and inhibition ratio of luminescence (IR) were reduced from 3.1x10(5) to 4 cfu/ml, 25265 to zero RLU/ml and 55 to -0.9%, respectively, which indicate that the treatment was very effective. The average removals of chemical oxygen demand (COD), soluble COD (SCOD), linear alkylbenzene sulfonates (LAS), suspended solids (SS), ammonia nitrogen (NH(3)-N), total nitrogen (TN) and total phosphorus (TP) were 92, 89, 96, 74, 67, 49 and 98%, respectively. The cost of all chemicals to treat a tonne of BHW was about 1.338 US$, with H(2)O(2) accounting for 74.7% of the total cost. The CF-FO combined process offers a safe, effective and feasible treatment for BMW, even if applied at low temperatures.
What problem does this paper attempt to address?