Influences of Grounding Site Soil Parameters on Earth Surface Potential of the High-voltage Interconnected Power Grid

WU Chao,WU Guang-ning,FAN Jian-bin,REN Zhi-chao,ZHANG Yi-kun
DOI: https://doi.org/10.13296/j.1001-1609.hva.2011.03.008
2011-01-01
Abstract:The HVDC grounding site selection,ground electrode design,and earth surface potential(ESP) distribution mainly depend on soil model,which is of great importance to analyze the influence of HVDC mono-polar operation with ground return on AC power grid.In this paper,the characteristics of the ESP under DC mono-polar operation mode were summarized with the software CEDGS according to the analysis of different soil models and variable soil parameters.The simulation results illustrate that the farther it is from the grounding site,the smaller the absolute value of ESP is with exponential attenuation.ESP shows approximately inverse proportion to soil thickness but direct proportion to resistivity of surface soil.Selections of soil model and its parameters exert significant influence on accuracy of ESP simulation,therefore the balance between accuracy and difficulty of calculation ought to be considered.