Soil Structure Analysis for Substation Sites

潘溪渊,曾嵘,何金良,高延庆
DOI: https://doi.org/10.3321/j.issn:1000-0054.2002.03.003
2002-01-01
Abstract:The multi layer soil structure model is used to design grounding systems of substations and power generating stations. The potential distribution of the ground surface due to a point current source is derived using electromagnetic field theory. The relationship between the apparent soil resistivity measured by the Wenner four poles method and the measurement pole span is also obtained. A nonlinear target function is introduced to transform the problem from the analysis of structural parameters to calculating the limited value of the nonlinear target function. After thorough research, one suitable method is used to calculate the soil structure parameters. The analysis software is applied to calculate actual substation sites' soil parameters, and the result in good agreement with the actual values.
What problem does this paper attempt to address?