Abstract:The multilayer soil structure model can not be easily used to design a grounding system and calculate its grounding resistance. Thereforce, a uniform soil model is needed that is equal to the multilayer soil structure. The simplification method for a two layer soil structure is proposed, and the influence of different parameters on the equivalent soil resistivity is analyzed. The equivalent soil resistivity of a multilayer soil structure depends on the soil parameters, the structure and the size of the grounding systems. The equivalent uniform soil model can be used to estimate the grounding resistance of a grounding system, but it can not be used to analyze the step and touch voltages.