Modeling and Electromagnetic Transient Simulation of UHV Autotransformer

曾麟钧,林湘宁,黄景光,郑峰,李智
DOI: https://doi.org/10.13334/j.0258-8013.pcsee.2010.01.015
2010-01-01
Abstract:To correctly apply transformer differential protection in the environment of ultra high voltage(UHV),it is necessary to model the UHV power transformer reasonably and carry out the corresponding electro-magnetic transient simulations.According to the equivalent circuit of three winding autotransformer,we set up the three winding autotransfomer model by means of unified magnetic equivalent circuit(UMEC)transformer model provided by EMTDC software.The parameters of UHV transformer arc converted to those of the UMEC model.By this way,the UHV transformer model is built.Under the UHV environment,the excitation and internal fault current of UHV power transformei are simulated,and the simulated data are utilized to investigate the operation reliability of the well-appfied differential protection combined with second order harmonic blocking.Simulation results show that the second order harmonic ratios of inrush currents through three phases of the UHV power transformer are all below 10%.In this case.the mal-operation of the differential protection cannot be avoided if the strategy that one phase current is applied to restrain three phases is adopted and the threshold of second order harmonic restraint ratio is 15%-20%.Besides,in some light fault conditions,the second harmonic ratio of the fault current is relatively high in the beginning of fault inception,leading to the short time delay of operation of protection.