Virtual Resistor Control Strategy of Parallel Active Power Filter with LCL Filter

CHEN Guo-zhu,ZHAO Wen-qiang
DOI: https://doi.org/10.13336/j.1003-6520.hve.2010.07.038
2010-01-01
Abstract:LCL filter,as a three-order one,is difficult to be stable. The active damping can effectively achieve the stable control instead of using damping resistance,and can effectively improve the efficiency of the system. We proposed a robust strategy for regulating the grid current entering grid from a shunt active power filter connected via a LCL filter. The strategy integrates an outer loop grid current regulator with inner capacitor current regulation or capacitor voltage regulation to stabilize the system. Based on this double-loop control scheme,high quality steady-state grid current waveform and fast-dynamic response can be obtained. Finally simulation validates the correction of the proposed control strategy.
What problem does this paper attempt to address?