Application of HF/UHF Joint Partial Discharge Analysis to On-Site Power Cable Terminal Detection

郭灿新,张连宏,姚林朋,钱勇,黄成军,江秀臣
DOI: https://doi.org/10.3969/j.issn.1006-6047.2010.05.020
2010-01-01
Abstract:The PD(Partial Discharge) method is employed to detect the potential insulation defect of high-voltage power cable terminal. According to the propagation characteristics of different PD signals,the PD sensors are developed based on HF(High Frequency) or UHF(Ultra High Frequency) detection principle,as well as the portable detection device. On-site test is carried out. The HF current transformer couples the PD current flowing through the ground strap and the UHF sensor is induced by the radiated the PD electromagnetic waves. The portable detection device is used to distinguish the real PD signals from interferences by pulse extraction and joint comparative analysis. The test results show that the HF/UHF joint analysis improves the effectiveness and veracity of PD identification.