Automatic switchover theory of stand-by transformer and its influence on economic operation mode of distribution substation

吴绪成,盛戈皞,王闻,徐剑,曾奕,江秀臣
DOI: https://doi.org/10.3969/j.issn.1006-6047.2010.04.015
2010-01-01
Abstract:The economic operation mode of distribution transformers interconnected at low voltage side to reduce distribution network loss is researched.The load switchover principle of distribution substation under economic operation mode is analyzed,the rules of load switehover point selection based on the minimal loss theory are proposed,and the working principle and action logic of the automatic switchover equipment at low-voltage side is presented.The transient process of three-phase transformer switching-on with and without load is mathematically modeled.With Matlab simulative calculation and practical analysis,the inrush excitation current of the switching-on without load and the impact current of switching-on with load are analyzed.Combined with the setting principles of instantaneous overcurrent protection and inverse time overcurrent protection,the influence of inrush current and impact current on the operating characteristics and parameter setting of transformer protections are studied.The reliability of power supply under economic operation mode of distribution transformers interconnected at low voltage side is verified.
What problem does this paper attempt to address?