Experimental Research on Anti-fouling of Heat Exchanger by Inserted Spring and Pulse Flow

Mei DOU,Sui-fei NAN,Pei-qing DUAN
DOI: https://doi.org/10.3969/j.issn.1003-9015.2010.05.028
2010-01-01
Abstract:The fouling behavior of the mixed salts scale crystallized from the DMF (N<N-dimethylformamide) solution during cooling in heat exchanger was investigated. The methods of inserting screw spring in cooling tube and using pulse flow by operating the feeding pump with running-stopping operation were adopted to prevent and clean up the fouling scale on the tube wall on-line. The variation of the heat transfer amount with the time prolongation of the experiments was obtained by measuring the temperature change of the cooling water at constant flow, and the total amount of the fouling scale, the crystallized mixed salts, was measured by weighting method. The effect of the inserted spring length, prolongations of pump running and stopping time respectively were studied. The results show that, in the experimental equipment with the inserted spring length of 175~198 cm, pump running time of 5~10 s and stopping time of 5 s, there is a remarkable anti-fouling effect; And in 4 hours heat transfer, the weight of fouling scale is decreased by 92.9% as compared with that of no inserted spring. At the same operating conditions, the weight of fouling scale changes only a little when the heat transfer experimental time are 4, 8 and 12 hours, respectively, which means that the method of anti-fouling is stable and effective.