Effects of Running Conditions on Fouling in Industrial Circulating Cooling Water System

Li Peng,Ping Xu,Yajun Zhang,Huizhen Wang
DOI: https://doi.org/10.16796/j.cnki.1000-3770.2016.04.011
2016-01-01
Abstract:To solve the problem of pipe scaling and microbial breeding by reuse water when it was used as circulating water.,we adopted the dynamic simulation device to simulate circulating cooling water system in this study.The foulant weight,EPS and PS,PN,total number of bacteria,slime-forming bacteria,IB and SRB in EPS affected by temperature,flow rate and concentration ratio was investigated.Results showed that more fouling occurred when increasing temperature.Specifically,total number of bacteria,slime-forming bacteria and iron bacteria reached its maximum at 35 ℃.The foulant weight remained steady with the variation of flow velocity.To be more specific,total number of bacteria,slime-forming bacteria,iron bacteria and SRB maximized at 0.8~1.0 m/s.Further,more fouling was observed when concentration increased.The concentration ratio with the value of 4.0 N showed the largest influence on the whole system.Suggestion was proposed that the system temperature should be controlled within 30 ℃,while the flow rate should greater than 1.0 m/s and the concentration ratio should avoid 4.0 N.