Research Progress on Parameters Measurement of Air Gap Discharge
ZENG Rong,GENG Yi-nan,NIU Ben,YU Zhan-qing,LI Zhi-zhao,WANG Feng
DOI: https://doi.org/10.13336/j.1003-6520.hve.2011.03.033
2011-01-01
Abstract:As the development of UHV in China recently,it is very urgent to fundamentally research the long air gap discharge.The nowadays research progress of the measurement system of electric field,transient current and streamer photograph is thus illustrated.First,the different kinds of sensor developed based on pockels effect are introduced,and the integrated electro-optic electric field sensor designed by the authors for intensive electric field measurement is presented.By implementing the output/input performance experiment,it can be found that the measurable amplitude of electric field reaches 24 kV/cm.The dynamic response performance of lightning and ns NEMP impulse is tested carefully,and the results show that the correlation coefficient between imposed impulse voltage and electric field is 0.9946.Combining the resistance with electro-optic modulator,a new transient current measurement system is developed and calibrated.Based on the 1 m rod-plane air gap test platform,the electric field,transient current and shape of streamer are investigated.The experimental results show that these measurement systems are suitable for the impulse electric field,transient current and shape observation of air gap discharge fundamental research.