Study on Light and Current Pulse Joint Detection Method of Corona Discharge in Air

Rixin Ye,Ming Dong,Jialin Liu,Lanjun Yang,Shi Kuang,Weizheng Zhang
DOI: https://doi.org/10.16790/j.cnki.1009-9239.im.2016.06.014
2016-01-01
Abstract:To evaluate the intensity of corona discharge in air, an optical and electrical partial discharge detection system was set up which could collect light and current pulse signals simultaneously. The typi-cal neddle-plate electrode defects were designed. By studying the characteristics of light and current pulse under different applied voltages, we found that the light and current pulse signals had good consistency in time. In the negative half cycle of discharge, the discharge repetition rate increases with the increase of applied voltage. In the positive half cycle of discharge, there is good linear relationship between the light pulse amplitude and apparent discharge magnitude, but there is unlinear relationship between the light pulse amplitude and apparent discharge magnitude when the voltage of positive half cycle is low. Furthermore, the PRPD spectra of light and current pulse presents"envelop"shape. Therefore, the inten-sity of corona discharge could be evaluated by the discharge repetition rate, pulse amplitude, and PRPD spectra tested by light and current pulse joint detection.