Experimental Research on Wide Frequency Transfer Characteristics of Voltage and Current Transformers in Substations

GONG Xue-hai,KONG Wei-zheng,YU Zhan-qing,YUAN Yi-chao,HE Jin-liang
DOI: https://doi.org/10.13336/j.1003-6520.hve.2009.07.009
2009-01-01
Abstract:The electromagnetic interference threatens the safe operation of substation,the main route of the electromagnetic disturbances generated in high voltage side of substation propagating into the secondary system is through the voltage and current transformers,the purpose of this paper is to build the transfer characteristic models of voltage and current transformers based on the measurements of actual voltage and current transformers.Firstly,the method to measure the scattering characteristic parameters and the conversion relation to the transfer characteristics was introduced by applying the network analyzer,the transfer characteristics of the CVTs and CTs with rated voltages of 110 kV,220 kV and 500 kV were measured,and the scattering characteristics and their differences of different types of voltage and current transformers with different rated voltage were analyzed.Then,the wide frequency transfer characteristics of voltage and current transformers were determined from experimental results,and the influence of voltage and current transformers on the propagation process of electromagnetic disturbances were analyzed.The analysis results show the transfer characteristics of different transformers have distinguished difference,but their resonance points widely distribute in the frequency range from hundreds kHz to several MHz,high disturbance energy would transfer to secondary side from the high voltage side in lots of special frequency points.These models provide the fundament for the estimation and analysis of electromagnetic interference in substation.
What problem does this paper attempt to address?