Simulation of Effect of Air Velocity Distribution on Performance of Two-Row Finned Tube Evaporator with One Flow Path

黄东,孙敏超,贾杰楠,吴蓓
DOI: https://doi.org/10.3321/j.issn:0253-987x.2009.05.008
2009-01-01
Abstract:The effects of the airflow with the same flow rate and different air front velocity distributions on the performance of a two-row finned tube evaporator were numerically studied by the software EVAP-COND 2.1.The air velocity distribution was in four shapes,such as rectangle,two triangles with upper and lower right angles,and isosceles triangle.The results showed that the evaporator capacity for the rectangle shape was the greatest and was 12% more than the smallest one for the triangle shape with lower right angle.The heat transfer performance of the first row tube caused by the local heat transfer coefficients distribution made a major contribution to the difference in the evaporator capacity.The maximum and minimum values of the heat transfer coefficients in the first row tube were smaller for the triangle with lower right angle than those for the other three air velocity shapes,leading to the smallest evaporator capacity.Moreover,the maximum value of the heat transfer coefficients in the first row tube was the greatest for the triangle with upper right angle,and the minimum was bigger than that for the triangle with lower right angle.Hence,the evaporator capacity for the triangle with upper right angle was only smaller than that for rectangle shape.In addition,the air velocity distribution had a smaller effect on the air-and-refrigerant temperature difference than on the heat transfer coefficient.