EFFECT OF THE AIR VELOCITY ON THE HEAT TRANSFER CAPACITY OF CONDENSER

DONG Yujun,CHEN Yunguang,BAO Tao,Hu Yueming,ZHOU Xiang,Yuan Xiuling
DOI: https://doi.org/10.3969/j.issn.1009-8402.2004.03.008
2004-01-01
Abstract:In this paper,a distributed parameter mathematical model of condenser was derived.On the basis of the model,a simulation code was implemented to calculat the performance of condensers with two or more tube depth rows.The effect of the air velocity on the heat transfer capacity of condenser was analyzed by calculating the air-side heat transfer coefficient,the changes of the temperature inside and outside tube at different air velocity.The results show that for the same areas the heat transfer capacity of condeser with two tube depth rows is 2.36% greater than that with four tube depth rows;and indicate that the decrease of row of tubes can intensify air-side average value ofheat transfer factor,as well as reducing the pressure drop.
What problem does this paper attempt to address?