Earth Surface Potential Distribution of HVDC Operation under Monopole Ground Return Mode

Zhiguo HAO,Yang YU,Baohui ZHANG,Linyan CHENG,Ruifeng CAO,Maosheng DING,Jun ZHANG
DOI: https://doi.org/10.3969/j.issn.1006-6047.2009.06.003
2009-01-01
Abstract:The long - range distribution features of ESP(Earth Surface Potential) of HVDC operation under monopole ground return mode are analyzed by finite element method,and the distributions of both shallow and deep soil structure models are calculated with ANSYS. The influences of substation outlet,substation earthing resistance,river and lake are taken into account. Results show that,soil structure has notable effect on surface potential and the computed result with the deep soil structure model is more accurate; the shorter the distance between substation overhead outline and grounding electrode is,or the longer the line is,or the fewer lines there are,the greater the potential difference between two line ends is. The river affects the ESP weakly while the edge of lake does comparatively strongly.
What problem does this paper attempt to address?