Experimental Investigation of Discharging Characteristics of Hollow Cathode Surge Protective Gap

YAO Xue-ling,CHEN Jing-liang,SUN Wei
DOI: https://doi.org/10.3969/j.issn.1003-6520.2007.10.006
2007-01-01
Abstract:The SPD(surge protective devices) were used as over-voltage protection devices in power system.In this paper,the surge protective gap based on hollow cathode effects was designed,the discharge curves were measured in air and nitrogen gas environment,and the critical pressure range was determined on condition that the voltage protective level Up was less than 4 kV.When the gap distance D and the hole diameter φ of HCSPG(hollow cathode surge protective gap) were all 3 mm,the working gas pressure which satisfy pulsed voltage protective level(Up=4 k) was from 5×101 Pa to 5×104 Pa.The experimental result can be derived that increasing the gap distances of the HCSPG can lead to the decrease of Up.While D=φ=3 mm and the nitrogen gas pressure is 6×102 Pa,the DC(the rise step of voltage waveform less than 1 kV/s) voltage protective level and pulsed protective level are 784 V and 2.14 kV respectively.The transferred charge per impulse produced by 10/350 μs pulsed current waveform is 48.26 C,and the ratio energy W/R is up to 2 MJ/Ω.It is testified that the HCSPG can be used as the SPD of class(B) in power system of AC 220 V and 380 V and other circumstances similarly.