Experimental Study of Effective Protective Distance of SPD

颜彪,陈水明,王顺超
DOI: https://doi.org/10.16511/j.cnki.qhdxxb.2011.12.028
2011-01-01
Abstract:The performance of one single Surge Protection Device(SPD) is studied experimentally in this paper.The effective protection distance of a given SPD is obtained for different types of load,namely,capacitive load,resistive load and inductive load.The experiments show that the oscillation phenomenon on the load is due to either the voltage wave reflection which is caused by the mismatch between the load impedance and the cable characteristic impedance or the resonance between the load and the cable.These phenomena lead to a high voltage at the end of a long cable and undermine the protection effectiveness of SPD.Moreover,the effective protection distance for different loads is obtained.