Improved frequency scanning of SSR risks in series-compensated UHVAC transmission systems
J. Man,X. Xie,Y. Luo,J. Tang,Y. Wang
DOI: https://doi.org/10.1049/icp.2020.0155
2020-01-01
Abstract:It is a great challenge to evaluate subsynchronous resonance (SSR) for a practical ultra-high-voltage alternative current (UHVAC) transmission system due to the huge number of operating conditions. Conventionally, frequency scanning is applied to the risky generators one by one to identify those operating conditions, under which the generator is vulnerable to SSR risks. However, this method requires massive calculation for analysing the stability of the system with multiple generators. To address this issue, this paper proposes an improved frequency scanning method for SSR stability analysis, with which the repeated calculation can be effectively avoided. The equivalent impedance network model of the entire system is established at first, wherein each generator is represented by its sub-transient reactance. Next, the electrical resonance frequency of the system under various operating conditions is obtained. Then, the operating condition of each generator that may cause SSR accidents can be obtained by comparing the generator’s torsional frequency and the electrical resonance frequency. Finally, the electromagnetic transient model (EMT) is established in PSCAD/EMTDC based on the thermal power system in Xilin Gol League of China, and the effectiveness and accuracy of the proposed method are validated by time-domain simulations.