Pilot-scale Experimental Study of NOxOUT Process

Ke-fu LI,Shao-hua WU,Zhen-zhong LI,Yang Wang,Jian-xun DONG,Yu-kun QIN
DOI: https://doi.org/10.3321/j.issn:0258-8013.2006.z1.020
2006-01-01
Abstract:Pilot-scale experiments of NOxOUT were carried out in CRF (combustion research facility) thermal state test rig. The temperature of real flue gas was measured by using a gas-extraction thermocouple. In a temperature range from 850-1000 °C, urea solution was injected into the post combustion flue gas of CRF through atomizing nozzle. The experimental results show that the NO reduction increased with increasing of n(NH3)/n(NO), optimum temperature of injected location for NOxOUT is 900 °C. With n(NH3)/n(NO) between 1.0 and 2.5, 65 %-89 % NO removal efficiency are obtained. Uncontrolled NO concentration lavel and residence time have important influence on NOxOUT process. Increasing uncontrolled NO concentration and residence time available increase the removal of NO.