A New Scheme of Faulty Line Selection with Adaptively Capturing the Feature Band for Power Distribution Networks

ZHAO Hui-mei,ZHANG Bao-hui,DUAN Jian-dong,ZHOU De-cai,ZHANG Wen-hao
DOI: https://doi.org/10.3321/j.issn:0258-8013.2006.02.008
2006-01-01
Abstract:The characteristic of three-phase current in a single-phase-to-ground distribution networks is analyzed. It is found that the ratio of the faulty component of faulty phase current to that of healthy phase current is no less than 2 for a faulty feeder, but less than 2 for a healthy feeder in a feature band, which varies with the structure of network and the mode of fault. Based on this principle, a new scheme of faulty line selection is presented. In this scheme, the sate of each feeder, namely healthy, faulty or “likely faulty”, was identified with the ratio of the faulty component of faulty phase current to that of healthy phase current firstly. If considered as “likely faulty”, the state of this feeder will be judged further with the ratio of transient current in an adaptive feature band, where the transient current of healthy phase is most centralized. Simulation of ATP and analysis of MATLAB proved that this scheme can distinguish faulty feeder from healthy feeder correctly with higher sensitiveness.
What problem does this paper attempt to address?