Mathematical Morphology Based Fault Detector and Improved Phase Selector in Power Swing

ZOU Li,ZHAO Qing-chun,LIN Xiang-ning,LIU Pei
DOI: https://doi.org/10.3321/j.issn:0258-8013.2006.13.007
2006-01-01
Abstract:The blocked protective relays should be able to respond to internal fault occurring during power swing blocking state. Therefore, it is necessary to distinguish faults from swing. It is also desirable to identify the fault phase correctly and rapidly during power swing so that distance relay can measure the impedance correctly and trip the fault selectively. The conventional sequence component fault phase selector mal-operates in some cases during power swing according to dynamic simulation results. In order to overcome the disadvantage, a fault detector and improved fault phase selector during power swing based on series multi-resolution morphological gradient (SMMG) transform are proposed in this paper. First, a SMMG filter is used to detect fault inception. If the fault is either a single or a double phase(s) to ground one according to the sequence component fault phase selection scheme, another SMMG filter is then employed to process three modular current signals so as to distinguish between them. Using EMTP, an extensive series of simulations has been carried out on a model system to verify the efficiency and feasibility of the proposed scheme.
What problem does this paper attempt to address?