Restraining Low Frequency Oscillation of Power System with IPC

LIU Xiu-kuan,JIANG Wei-yong,ZHOU Su-quan,WANG Qi,LIU Zhuo
DOI: https://doi.org/10.3969/j.issn.1006-6047.2006.01.001
2006-01-01
Abstract:The circuit of IPC(Interphase Power Controller)is discussed and a linear model of the power system with an IPC in one transmission line is given.Based on the model,the form and properties of torque provided by IPC are analyzed.Analysis shows that IPC provides no positive damping torque but negative synchronus torque,which is disadvantageous to power systm stability.By adjusting IPC parameters with appropriate control strategy,positive synchronous torque and damping torque can be provided to keep power system syn-chronization and damp power system oscillation.