DYNAMIC BEHAVIOR OF IPC AND POWER SYSTEM ON BOTH SIDES CONSIDERING THE VARIATION OF LOAD FREQUENCY

李娟,刘修宽,曲祖义,纪延超,柳焯
DOI: https://doi.org/10.3321/j.issn:0258-8013.2003.07.015
2003-01-01
Abstract:This paper studies the dynamic behavior of both sides network and IPC, when the load and frequency vary. Whether both sides of the tie line with IPC are easy to fall into the state of asynchronism is explored emphatically. The dynamic load flow with frequency difference, the basic equations of voltage and current of IPC, and the tracking equivalent technology of network are combined for a special mathematical model to break through the technical difficulty. On the background of practical interconnected network, the research results show that the state of the relative phase slippage can not easily be turned into asynchronous state because of the difference of the frequency variable step, while the loads of the two sides normally vary. It is indicated that the power variety of tie-line with IPC can adapt to the change need of network load ,and that both sides of interconnected network can run placidly with small frequency difference, if the operation point lies on the adaptability section of the P-d curve.
What problem does this paper attempt to address?