MOA Action Influence Tie-Line Power Control of Interconnected Power System with IPC

LIU Xiu-kuan,ZHOU Su-quan,WANG Qi,LIU Zhuo
DOI: https://doi.org/10.3969/j.issn.1007-449x.2006.05.006
2006-01-01
Abstract:This paper discussed the influence of power control because of the voltage protected on the interconnect power system with IPC(inter-phase power controller).And the adjust and control circuit model was established based on the simple circuit of large power system.The arresters were posed on the send port,the receive port and the output port between the IPC's capacitor and reactor.The operating voltage of each nodes was calculated and the MOA(metal oxide arrester) action influencing the tie-line power control of interconnected power system with IPC was researched.The simulation result indicated that the MOA act more the tie-line power vary less with the change of IPC's parameter.
What problem does this paper attempt to address?