Prediction of the Performance of Flooded Refrigerant Evaporators Based on a Distributed Parameter Model

黄兴华,王启杰,王如竹
DOI: https://doi.org/10.3321/j.issn:1006-2467.2004.07.030
2004-01-01
Abstract:Based on the Chen two-phase forced-convection boiling model, a theoretical model with distribution parameters was developed for predicting the performance of flooded refrigerant evaporators (FRE). With this model, the effect of refrigerant pressure drop across tube rows on the refrigerant local saturation temperature is accounted. The pressure drop is calculated using the separated flow model. The Chen model is used to predict the boiling heat transfer coefficient. For FRE with bottom-to-top pass arrangement, the model improves the previous Webb's method, and the effect of no uniform distribution of refrigerant flow along the tube on the performance is accounted. An incremental, iteration calculation procedure is outlined. The model was applied to predict the performance of a commercial FRE with side-to-side water pass arrangement, and the effects of different tubes and pass arrangements on evaporator performance were analyzed. The predicted total heat transfer rate of the commercial FRE agrees well with the experimental data.
What problem does this paper attempt to address?