A Three-Zone Analytical Model For Performance Prediction Of A Brazed Aluminum Evaporator Operating Under Dehumidifying Condition - Part 1 - Analysis Method

Xiaomin Wu,Jingchun Min,Ralph L. Webb,Weicheng Wang
2001-01-01
Abstract:An analytical model for predicting the performance of a brazed aluminum evaporator operating under dehumidifying conditions was proposed. The evaporator uses multi-channel flat tubes and louver fins. In the model, the in-tube refrigerant flow was divided into three regions including the two-phase, liquid deficient and superheat regions. For each region, proper correlations were adopted to calculate the local heat transfer and pressure drop. The pressure drop inside the tube, pressure losses at the tube entrance and exit and pressure drop inside the header were all taken into account in the heat transfer calculations. The airside fin surfaces were assumed to be fully wetted by condensate. The sensible heat transfer coefficient and pressure drop of the wet louver fin were obtained by assuming them to be the same as those of the dry louver fin, which were calculated using the Webb semi-analytical correlations. The basis for this assumption is our test data showing that the sensible heat transfer coefficient and pressure drop of the wet louver fin were nearly equal to those of the dry louver fin in the case that the fin was coated with a hydrophilic coating. I he overall beat transfer coefficient was calculated using the enthalpy driving potential method.