Liquid Desiccant Total Heat Recovery System with Single-Stage Spray Unit for Outdoor Air Handler

刘晓华,李震,江亿,陈晓阳
DOI: https://doi.org/10.3321/j.issn:1000-0054.2004.12.013
2004-01-01
Abstract:In air conditioning system, an increased outdoor air flow rate improves the indoor air quality but also increases the energy consumption of the fan. This paper describes a liquid desiccant total heat recovery device combined with a single-stage sprayed module for an outdoor air handling unit. The liquid desiccant total heat recovery device has higher efficiency and avoids cross contamination of the air streams. Average electrical and thermal coefficient of performance (COP) of the air processor are 9.4 and 3.0 in summer with an average thermal COP of 2.2 in winter. With the current energy prices in Beijing, the operating cost of the new outdoor air handler is about 75% of the cost of a conventional outdoor air handler in the summer and 25% of that in the winter.
What problem does this paper attempt to address?