Application Of Heat Pump-Driven Two-Stage Desiccant Wheel System In Office Buildings

Rang Tu,Xiaohua Liu,Tao Zhang,Yi Jiang
2014-01-01
Abstract:Multi-stage desiccant wheel systems are an effective way to increase the performance of desiccant dehumidification. In this paper, a heat pumpdriven two-stage desiccant wheel (HPTW) system is proposed. Between two adjacent desiccant wheels, an evaporator is inserted at the processed air side to provide cooling capacity for dehumidification, and a condenser is inserted at the regeneration air side to provide heat capacity for regeneration. A low regeneration temperature under 50 degrees C(122 degrees F) can be realized, and the system COP is higher than 4, which is better than traditional condensation dehumidification methods or single-stage desiccant wheel systems; the lower the humidity ratio of the processed outdoor air, the higher the COP of the two-stage desiccant wheel system. The proposed HPTW system can be applied in office buildings for dehumidification to realize temperature and humidity independent control, and a high evaporating temperature chiller (HEC) can be used to deal with the sensible heat load. The performance of the HPTW and HEC system is simulated in a typical office building in Beijing and Guangzhou. The hour-by-hour sensible and latent loads of the building are calculated using DeST software. The annual energy consumption of the HPTW and HEC system is analyzed and compared with that of a traditional HVAC system using a low evaporating temperature chiller (LEC). The results show that the energy-saving potential of the proposed system is around 15-35% compared to the conventional system.
What problem does this paper attempt to address?