System principle and performance tests of a heat pump driven two-stage liquid desiccant outdoor air handler

Liu Shuanqiang,Jiang Yi,Chen Xiaoyang
DOI: https://doi.org/10.3969/j.issn.1002-8501.2008.01.014
2008-01-01
Abstract:Presents the principle and the operation mode of the novel two-stage liquid desiccant outdoor air handler,and primarily describes the testing data of performance of its main parts.The testing data show that the latent heat recovery efficiency and the total heat recovery efficiency of the unit is about 55%,the full load COP of the outdoor air handler is 5.0,and even over 5.9 under part load conditions.Besides,the full load COP of the integrated heat pump is 4.01,and the part load COP can be as high as 5.72.The sensible heat recovery efficiency of the solution heat exchanger is over 80 percent.Tests and analyses the overall performance of the outdoor air handler,and points out the importance of the water makeup in the regeneration units.
What problem does this paper attempt to address?