Performance Optimization Analysis of the Composite Liquid Desiccant Evaporative Cooling Air-Conditioning System

刘雄,王春苗,程立娜
DOI: https://doi.org/10.3969/j.issn.1006-7930.2009.03.021
2009-01-01
Abstract:A new evaporative air-conditioning refrigeration system using two-step liquid desiccant was presented.It could operate whole year and recover the heat or cooling energy from indoor exhaust air.Compared with the similar one-step dehumidifying system,it has higher operation efficiency.The result from computation and analysis indicates :Evaporator is the main influence factor.For improving the coefficient of performance of the whole system,evaporator,evaporative condenser and evaporative fluid cooler should be devised and matched by winter operating mode.When the entrance solution concentration of dehumidifier,the flux proportion between dehumidifiers,and the flux proportion of outside circulates respectively is 30%,0.25 and 0.15,the coefficient of performance is optimum.Under air conditioning,outdoor computation parameters in Xi'an,the coefficient of performance of the whole system is 0.791 and the entrance solution temperature of regenerater is 48.5 ℃.