AN INTEGRATED CONTROLLER OF MULTI-TAP ARC-SUPPRESSION WITH VARIATIONAL DAMP AND DETECTION OF EARTH FAULT FEEDER

蔡旭,李仕平,杜永忠,陈刚
DOI: https://doi.org/10.3321/j.issn:1000-1026.2004.05.019
2004-01-01
Abstract:By connecting damp resistor to the secondary assistant winding of arc-suppression, the question of easily destroyed damp resistor is solved. The equivalent damp resistance changes with the variety of the tap of arc-suppression. So another train of thoughts is needed to calculate the value of the damp resistor and control the arc-suppression. A method of choosing secondary damp resistance is proposed. The method of measuring the single-phase-to-earth capacitive current of the power network by measuring the neutral point current is presented, the principle of controlling one or more arc-suppressions is investigated, a principle based on zero sequence current increment function for detecting grounded feeder is put forward. A controller for arc-suppression with variation of damp and detection of earth fault feeder is developed. Sets of such equipment have been implemented steadily for many years in power networks, and the compensation effect is satisfied and the result of detecting fault feeders is correct.
What problem does this paper attempt to address?