Cooperative Control Scheme for Phase Lock Loop and Load Sharing in Parallel Operation of UPS with No Control Interconnections
LIN Xin-chun,DUAN Shan-xu,KANG Yong
DOI: https://doi.org/10.3969/j.issn.1003-3076.2007.04.011
2007-01-01
Abstract:In the parallel operation of UPS with no control interconnections, the droop characteristic is widely adopted as the current-sharing control strategy. However, as the phase lock loop and the frequency droop characteristic may simultaneously change the inverter's output frequency when power supply is normal, there may be disturbance between the phase lock loop and the frequency droop characteristic, which may cause oscillation or even instability of the UPS paralleled system. Aiming at this disturbance, this paper presents a cooperative control scheme, which not only can completely eliminate the disturbance between the phase lock loop and the frequency droop characteristic, but also can achieve good load-sharing, and at the same time the presented cooperative control scheme also can achieve high utility phase tracking precision. The dynamic and static experimental results for different loads are presented for two paralleled UPS with no control interconnections, which prove the feasibility of the proposed control scheme.