Instantaneous Current-Sharing Control Strategy for Parallel Operation of UPS Modules Using Virtual Impedance
Yu Zhang,Mi Yu,Fangrui Liu,Yong Kang
DOI: https://doi.org/10.1109/tpel.2012.2200108
IF: 5.967
2012-01-01
IEEE Transactions on Power Electronics
Abstract:By regulating the inverter output current every switching cycle, instantaneous current-sharing control strategies are usually employed in paralleled modular uninterruptible power supplies (UPSs). In this paper, virtual impedance, which is usually utilized in the droop method, is firstly introduced to the instantaneous current-sharing control strategy to achieve good load current-sharing performance. The instantaneous circulating current model of the paralleled system is developed and the circulating impedance is derived as well to clearly identify the intrinsic nature of unequal sharing of load current. By inserting the virtual impedance to the circulating impedance with the help of proper control strategy, good current-sharing capability can be obtained. The parallel inductor, e. g., coupled inductor, which is generally added at the output of each inverter to reduce the circulating current among modules, can be, therefore, eliminated, contributing to reduced weight, volume, and cost. In the meantime, the system output-voltage regulation performance, e. g., amplitude and waveform quality, is not affected by the introduction of the virtual impedance. The designation of the virtual impedance is provided and its implementation is simple but rather effective. Experimental results are also provided to verify the feasibility of the proposed method.