STUDY ON THE AGING OF STATOR INSULATION OF LARGE GENERATORS USING THERMOANALYSIS

鲍棋铭,高乃奎,马小芹,张亮,谢恒堃
DOI: https://doi.org/10.3321/j.issn:0258-8013.2003.07.021
2003-01-01
Abstract:The aging of stator insulation of large generators has great relation with appearance and development of micro defects inside the insulation ,and deterioration of epoxy. In this paper, Thermogravimetry (TG) and Differential Scanning Calorimeter (DSC) analysis are applied to the study on the aging of stator insulation of large generators. The results show that, compared with that of the sound parts, epoxy content and starting oxidation temperature of the defective parts presented much more remarkable changes in its physical and chemical performance. In detail, its content and starting-temperature of oxidation decreased obviously; furthermore, its decomposition-activation energy DE of epoxy in the defective parts increased evidently. It is considered that the aging of epoxy caused by multi-stresses is the main reason for the generation and development of defects and the final aging of the main insulation structure of large generators.
What problem does this paper attempt to address?