RELIABLE LIFE ASSESMENT OF STATOR INSULATION FOR LARGE GENERATORS USING ULTRASONIC VELOCITY
HAO Yan-peng,XIE Heng-kun,WANG Guo-li,GAO Nai-kui
DOI: https://doi.org/10.3321/j.issn:0258-8013.2005.04.014
2005-01-01
Abstract:To assess the remaining life of large generator stator insulation effectually, lots of stator bars from three 300MW generators, which had been in-service for 16, 18 and 23 year periods respectively, were tested to diagnose the insulation condition. The measured parameters included statistical minimum ultrasonic velocity Vmin, statistical average ultrasonic velocity Vav, dissipation factor tip-up ?tanδ, change of capacitance ?C/C0, maximum discharge magnitude qmax and mean discharge magnitude qmean. With linear regression analysis A compared investigation of the correlation between Vmin, Vav and time in service y?was compared with that between ?tanδ, ?C/C0, qmax, qmean and y? respectively. The results showed that a significant correlation was evinced between Vmin, Vav and y?, that a most slight correlation between ?tanδ、qmax, qmean and y?, and that no definite correlation between ?C/C0 and y?. Vmin and Vav were of more accuracy than ?tanδ、qmax, qmean and ?C/C0 to assess stator insulation. A second-order and a third-order mathematic models were built to describe the relationships of Vmin, Vav with y?respectively. Based on the two models, predicted methods were proposed to assess the most reliable and the 95% reliable remaining life of stator insulation respectively.