INSULATION CONDITION DIAGNOSIS OF LARGE GENERATOR STATOR BARS BASED ON ULTRASONIC PULSE-ECHO METHOD

郝艳捧,闫波,王国利,谢恒堃,高乃奎
DOI: https://doi.org/10.3321/j.issn:0258-8013.2003.04.019
2003-01-01
Abstract:An ultrasonic pulse-echo method was put forward to diagnose insulation condition of generator stator bars. Based on this method, a statistical minimal velocity, a statistical average velocity, and an attenuation coefficient of ultrasonic longitudinal waves propagated in stator insulation were measured, and a statistical defect rate were measured also. Three sets of stator bars in-service for 16, 18 and 23 year periods respectively in three generators (300MW, 18kV) and a new stator bar were tested in laboratory, several stator windings in a generator were also tested to examine the on-site testing capability of this method. The experimental results indicated that statistical minimal velocity and statistical average velocity decrease with insulation in-service time, the decrease of statistical minimal velocity is larger than that of statistical average velocity, and that statistical defect rate measured on sever-aged insulation is greater. The on-site ultrasonic testing results demonstrated that two velocity parameters are measured practically in the condition of generator light maintenance. It is effective and practical to use ultrasonic pulse-echo method for insulation condition diagnosis of generator stator bars.