IGCT-Based Fault Current Limiter for Three- Phase Power System with Grounded Neutral and Its Control Strategy
FEI Wan-min,ZHANG Yan-li,LU Zheng-yu
DOI: https://doi.org/10.3321/j.issn:1000-3673.2006.11.018
2006-01-01
Abstract:It is proposed that the half-controllable switching elements, namely the SCRs, in bridge type short circuit current limiter, in which bypass inductances are equipped, for three-phase neutral grounded power system are substituted by integrated gate commutated thyristors (IGCTs). This way, the runaway time of the inversion bridge circuit is shortened from half a period to that within the time-delay interval of measuring circuit, thus the inductance of DC reactor can be evidently reduced and it leads to that the volume of DC reactor, which takes the majority of weight and cost of fault current limiter, can be reduced by 1/9.6 times, as a result, weight and volume of fault current limiter (FCL) can greatly descend. The simulation of IGCT based short circuit FCL and its control strategy under different types of faults, i.e., the single phase short circuit, two-phase short circuit and three-phase short circuit, is conducted, simulation results show that the proposed FCL and its control strategy are effective and practicable.