Transient Current Measurement for Power System by Using Improved AC/DC Current Transformer

任士焱,张智杰,刘晓军
DOI: https://doi.org/10.3321/j.issn:1671-4512.2001.11.031
2001-01-01
Abstract:The transient current measurement by the improved AC/DC comparator is developed. The important design basis for transient current measurement of the current comparator used in the power system are given. The improved AC/DC comparator consists of a self-balancing DC comparator and an electronically compensated AC transformer. The transient performance details and calculation formulas of the comparator are analyzed and derived. The testing results show that the transient errors of 5000 A AC/DC transformer are less than 1 percent while the errors of conventional transient current transformers reach 5-10 percent and even more.
What problem does this paper attempt to address?